Type | Standard | lEC/EN 61009-1 | |
Electrical features |
Poles | P | 1P+N, 3P+N |
Type(wave form of the earth leakage sensed) | A, AC, S | ||
Thermo-magnetic release characteristic | B, C, D | ||
Rated current In | A | 1, 2, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 | |
Rated voltage Ue | V | 230/400 | |
Rated sensitivity lΔn | A | 0.03, 0.05, 0.1, 0.3 | |
Rated residual making and
breaking capacity lΔm |
A | 500(In≤40A) 630(In>40A) | |
Rated short-circuit capacity lcn | A | 10000 | |
Break time under lΔn | s | ≤0.1 | |
Rated frequency | Hz | 50/60 | |
Rated impulse withstand voltage(1.2/50)Uimp | V | 4000 | |
Dielectric test voltage at ind. Freq. for 1min | kV | 2 | |
Insulation voltage Ui | V | 500 | |
Pollution degree | 2 | ||
Mechanical features |
Electrical life | t | 2000 |
Mechanical life | t | 10000 | |
Contact position indicator | Yes | ||
Protection grade | IP20 | ||
Ambient temperature
(with daily average≤35℃) |
℃ |
-5~+40 |
|
Storage temperature | ℃ | -25~+70 | |
Installation |
Terminal connection type | Cable/Pin-type busbar/U-type bar | |
Terminal size top / bottom for cable |
mm2 | 25 | |
AWG | 18/3 | ||
Terminal size top / bottom for busbar |
mm2 | 25 | |
AWG | 18/3 | ||
Tightening torque |
N*m | 2.5 | |
In-Ibs | 22 | ||
Mounting | On DIN rail EN 60715(35mm)by means of fast clip device | ||
Connection | From top |